1. ES200 s capable of measuring insulation resistance, and also innovatively increases the voltage measurement function.
2. Equipped with standard resistance, in the comparison measurement mode, the measured resistance value is compared with the standard resistance to ensure the measurement accuracy.
3. Three measurement modes: timing measurement, comparison measurement, continuous measurement and omnidirectional measurement.
ES200 SPECIFICATION | |
Battery | 3150mAh |
Display | 5'' |
Working Temperature | 0~50℃ |
Dimensions | 180*174*65.5(mm) |
Weight | 1.7kg |
AC AND DC VOLTAGE TEST PERFORMANCE PARAMETERS | ||
Voltage Type | DC Voltage | AC Voltage |
Measuring Range | ±30~±600V | 30~600V(50/60Hz) |
Resolution | 1V | 1V |
Measurement Accuracy | ±3% | ±3% |
INSULATION RESISTANCE TEST PERFORMANCE PARAMETERS | ||||
Test Voltage | 500V | 1000V | 2000V | 5000V |
Measuring Range | 0.0MΩ~20GΩ | 0.0MΩ~40GΩ | 0.0MΩ~100GΩ | 0.0MΩ~1000GΩ |
Open Circuit Voltage | DC500V(0~20%) | DC1000V(0~20%) | DC2000V(0~20%) | DC5000V(0~20%) |
Measurement Accuracy | 0.0~99.9MΩ: ±(3%+5) 100MΩ~9.99GΩ: ±(5%+5) 10.0GΩ~20.0GΩ: ±(10%+5) | 0.0~99.9MΩ: ±(3%+5) 100MΩ~9.99GΩ: ±(5%+5) 10.0GΩ~40.0GΩ: ±(10%+5) | 0.0~99.9MΩ: ±(3%+5) 100MΩ~9.99GΩ: ±(5%+5) 10.0GΩ~100GΩ: ±(10%+5) | 0.0~99.9MΩ: ±(3%+5) 100MΩ~9.99GΩ: ±(5%+5) 10.0GΩ~99.9G: ±Ω(10%+5) |
Short Circuit Current | <3.0mA |